CJX1 AC Contactors
CJX1 < 3tf > electrical magetic contactor products are AC 50 Hz or 60 Hz. The magetic contactor rated insulation voltage is 690-1000v. Under the category of AC3, when the rated working voltage is 380V, the magnetic contactor rated working current is 9A-400A. The AC contactor is mainly used for remote connecting and breaking circuit.The electrical magetic contactor is suitable for controlling the starting of AC motor. Stop and reverse, The Contactor is in line with IEC947, VDE0660, GB14048 and other standards
- Description
- Inquiry
2. CJX1 AC Contactors Specification
Type | CJX1-9 CJX1-12 | CJX1-16 CJX1-22 | CJX1-32 | CJX1-45 CJX1-63 | CJX1-75 CJX1-85 | CJX1-110 CJX1-140 | CJX1-170 CJX1-205 | CJX1-250 CJX1-300 | CJX1-400 CJX1-475 | |
---|---|---|---|---|---|---|---|---|---|---|
Mechanicalendurance(×106) | 10 | 10 | 10 | 8 | 8 | 8 | 8 | 8 | 8 | |
Conventionalthermal current(A) | 20 | 30 | 45 | 80 | 100 | 160 | 210 | 300 | 400/550 | |
Rated insulationvoltage(V) | 660 | 660 | 660 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
Rated(380V)operatingcurrent(A) | AC-3 | 9/12 | 16/22 | 32 | 45/63 | 75/85 | 110/140 | 170/205 | 250/300 | 400/475 |
AC-4 | 3.3/4.3 | 7.7/8.5 | 15.6 | 24/28 | 34/42 | 54/68 | 75/96 | 110/125 | 150 | |
Power ofcontrollablemotor(KW)AC-3 | 380V | 4/5.5 | 7.5/11 | 15 | 22/30 | 37/45 | 55/75 | 90/110 | 132/160 | 200/250 |
660V | 5.5/7.5 | 11 | 23 | 39/55 | 67 | 100 | 156 | 235 | 375 | |
Power ofcontrollablemotor(KW)AC-4 | 380V | 1.4/1.9 | 3.5/4 | 7.5 | 12/14 | 17/21 | 27/35 | 38/50 | 58/66 | 81 |
660V | 2.4/3.3 | 6/6.6 | 13 | 20.8/24 | 29.5/36 | 46.9/60 | 66/86 | 100/114 | 140 | |
Frequencyof operation(l/h) | AC3 | 1000 | 750 | 750 | 1200/1000 | 1000/850 | 1000/750 | 700/500 | 700/500 | 500/420 |
AC4 | 250 | 250 | 250 | 400/300 | 300/250 | 300/200 | 200/130 | 200/130 | 150 | |
Electricalendurance(×106) | AC3 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 |
AC4 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | |
Operating voltagerange of coil | (0.8~1.1)Ue | |||||||||
Powerconsump-tion of coil | Atracting(VA) | 10 | 10 | 12.1 | 17 | 32 | 39 | 58 | 84 | 115 |
Starting(VA) | 68 | 69 | 101 | 183 | 330 | 550 | 910 | 1430 | 2450 | |
Rated insulationvoltage of auxitiarycontacts(V) | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | |
Conventionalthermal current ofauxitiary contacts(A) | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | |
Ratedoperatingcurrent ofauxitiarycontacts(A) | AC15380/220 | 6/10 | 6/10 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 |
DC13220V | 0.45 | 0.45 | 0.48 | 0.48 | 0.48 | 0.48 | 0.48 | 0.48 | 0.48 | |
Ratedvoltage ofthe controlcoil(V) | 50Hz | 24,36,48,110,127,220,380,etc | ||||||||
60Hz | 24,110,220,440,etc. |
3. CJX1 AC Outline and Mounting Dimension
Type | A max | B max | C max | a | b |
CJX1-9,12 | 45 | 78.5 | 104(90) | 35+0.31 | 60+0.37 |
CJX1-16,22 | 46 | 85 | 114 | 35+0.31 | 75+0.37 |
CJX1-32 | 74 | 85 | 108 | 50+0.31 | 75+0.37 |
Type | A max | B max | C max | a | b | φ |
CJX1-45,63 | 91(114) | 120 | 124 | 70+0.6 | 100+0.2 | 4.8 |
CJX1-75,85 | 102(125) | 135 | 142 | 80+0.6 | 100+0.2 | 5.5 |
CJX1-110,140 | 122(145) | 156 | 154 | 100+0.2 | 130+0.8 | 6.5 |
CJX1-170,205 | 140(163) | 185 | 190 | 100+0.2 | 160+0.8 | 7 |
CJX1-250,300 | 150(173) | 205 | 200 | 120+0.2 | 180+0.8 | 9 |
CJX1-400,475 | 165(188) | 205 | 225 | 130+0.8 | 180+0.8 | 9 |