SL1-63(ID) Residual Current Circuit Breaker (RCCB)

SL1-63(ID) residual current operated circuit breaker (without overcurrent protection) is applicable to lines with AC 50Hz, rated voltage of two poles 230V and four poles 400V, and rated current up to 63A.

 

  • Description
  • Inquiry

SL1-63(ID) Residual Current Circuit Breaker (RCCB) (without overcurrent protection) is applicable to lines with AC 50Hz, rated voltage of two poles 230V and four poles 400V, and rated current up to 100A. When personal electric shock or grid leakage current exceeds the specified value, theResidual Current Circuit Breaker (RCCB) can quickly cut off the fault power supply in a very short time to protect the safety of personal and electrical equipment, It can also be used for infrequent line conversion.

SL1-63(ID) residual current operated circuit breaker  Usage environment

1.The ambient temperature is – 5 ℃ to + 40 ℃, and the average value within 24 hours does not exceed 35 ℃;
2.The altitude shall not exceed 2000m
3.When the ambient temperature is 40 ℃, the relative humidity does not exceed 50%, and when the average monthly temperature of the wettest month does not exceed 25 ℃, the relative humidity does not exceed 90%
4.The pollution level is grade II
5.The installation category is II and III
6.The installation type is standard guide rail installation
safety of personal and electrical equipment, It can also be used for infrequent line conversion.

SL1-63(ID) residual current operated circuit breaker classification

This product can be divided into AC type and a type.

AC type: the AC leakage signal is detected in the zero sequence current transformer, amplified by the integrated circuit board, the product trips and cuts off the line, so as to protect the line equipment and personal safety.

Type A: residual current protection circuit breaker for AC and DC pulsating component fault current. Higher security, wider range. Type a residual current circuit breaker is widely used in many European countries.

 

TypeStandardIEC/EN 61008-1
Electrical featuresLeakage typeElectromagnetic type
Rated current InA16, 25, 32,40, 50, 63, 80,100
Type (wave form of the earth leakage sensed)A, AC
PolesP2,4
Rated voltage UeV240/415
Insulation voltage UiV500
Rated frequencyHz50/60
Rated breaking capacity Inc=IcA6000,10000
SCPD fuseA10000
Rated impulse withstand voltage (1.2/50) UimpV6000
Dielectric test voltage at ind. Freq, for lminkV2.5
Rated sensitivity InA0.03, 0.1, 0.3
Rated residual making and breaking capacity ImA500(In <40A); 630In=63A);1000(In=80A/100A)
Pollution degree2
Mechanical featuresElectrical lifet4000
Mechanical lifet8000
Protection degreeIP20
Storage temperature°C-95
Ambient temperature (with daily average<35°C)°C5~+40
InstallationTerminal connection typeCable/Pin-type busbar
Terminal size top / bottom for cablemm225/35
AWG18-3/18-2
Terminal size top / bottom for busbarmm210/16
AWG18-8/18-5
Tightening torqueN*m2.5
In-Ibs22
MountingOn DIN rail EN 60715(35mm)by means of fast dip device
ConnectionFrom top and bottom

SL1-63(ID) residual current operated circuit breaker  Dimension

Contact Us